16 kVA, 11 kV, inland
Oil immersed, three phase, medium voltage to low voltage. Pole mounted, in inland specification. Wound, assembled, filled, tested and finished at Botshabelo.

- Rated power
- 16 kVA
- HV
- 11 kV
- LV
- 240 V
- Standard
- SANS 780
Pole mounted, inland
Specified in suburban, township and rural environments where high voltage overhead reticulation remains in service. Mounted on the pole itself, out of reach and out of the way.
Built in inland specification. If this unit is going to the coast, ask us for the coastal build instead: coastal air is corrosive and an inland unit will not last there.
How every unit is tested| Rated power | 16 kVA |
| HV | 11 kV |
| LV | 240 V |
| Phases | 3 |
| Frequency | 50 Hz |
| Impedance | 3.5% |
| No load losses | 65 W |
| Load losses at 75°C | 400 W |
| Winding conductor | Aluminium |
| Cooling | ONAN |
| Tap changer | Off load, ±2 x 2.5% |
| Standard | SANS 780 |
| Oil | SANS 555 |
| Construction | Hermetically sealed, non breathing |
| Tank finish | Sandblasted, zinc 60µ, epoxy powder 40µ |
| Max altitude | 1 800 m |
| Ambient | 40 °C |
This unit is tested before it leaves
Routine production tests are carried out on every unit before dispatch, from winding resistance through to rating plate verification. The plate on this transformer is checked against the build for rating, vector group, impedance and serial number before release.
See the full test schedule- Winding resistanceJoints, connections
- Insulation resistanceMoisture, contamination
- Turns ratioTap connections
- Polarity, vector groupDyn11
- Applied voltage withstandMain insulation
- Rating plate verificationPlate against build
Other units in the range
Quote this unit
Tell us the quantity and where it is going. We will come back to you with a price and a lead time.