315 kVA, 11 kV, inland
Oil immersed, three phase, medium voltage to low voltage. Ground mounted, in inland specification. Wound, assembled, filled, tested and finished at Botshabelo.

- Rated power
- 315 kVA
- HV
- 11 kV
- LV
- 415 V
- Standard
- SANS 780
Ground mounted, inland
For higher load distribution where a plinth or enclosure is practical, feeding industrial, commercial and municipal loads.
Built in inland specification. If this unit is going to the coast, ask us for the coastal build instead: coastal air is corrosive and an inland unit will not last there.
How every unit is tested| Rated power | 315 kVA |
| HV | 11 kV |
| LV | 415 V |
| Phases | 3 |
| Frequency | 50 Hz |
| Vector group | Dyn11 |
| Impedance | 4.5% |
| No load losses | 550 W |
| Load losses at 75°C | 3800 W |
| Winding conductor | Aluminium |
| Cooling | ONAN |
| Tap changer | Off load, ±2 x 2.5% |
| Standard | SANS 780 |
| Oil | SANS 555 |
| Construction | Hermetically sealed, non breathing |
| Tank finish | Sandblasted, zinc 60µ, epoxy powder 40µ |
| Max altitude | 1 800 m |
| Ambient | 40 °C |
This unit is tested before it leaves
Routine production tests are carried out on every unit before dispatch, from winding resistance through to rating plate verification. The plate on this transformer is checked against the build for rating, vector group, impedance and serial number before release.
See the full test schedule- Winding resistanceJoints, connections
- Insulation resistanceMoisture, contamination
- Turns ratioTap connections
- Polarity, vector groupDyn11
- Applied voltage withstandMain insulation
- Rating plate verificationPlate against build
Other units in the range
Quote this unit
Tell us the quantity and where it is going. We will come back to you with a price and a lead time.